Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03736 10/19/07
1. Provide proper overcurrent protection for Gas Heater Unit. THIS COMMENT WAS MADE ON THE PREVIOUS SUBMITTAL. Suggest you fuse the disconnecting means for 6A. Reference NEC 430 Part III, 240.6.
2. Demonstrate compliance with Tucson Lighting Code. THIS COMMENT WAS MADE ON BOTH PREVIOUS SUBMITTALS. Add the Schedule per Section 8 of the Code.
3. Demonstrate compliance with NEC 700.12 (F) regarding the circuiting of the exit and egress lighting. THIS COMMENT WAS MADE ON THE PREVIOUS SUBMITTAL. Please read the following from the referenced Code Section: "The branch circuit that feeding the unit equipment shall be the same branch circuit as that serving the normal lighting in the area and connected ahead of any local switches."