Permit Number: T07CM03736
Parcel: 13001004B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03736
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03736 10/15/07
1. Mechanical shall provide Unit Heater Blower specifications and electrical requirements. Comment made on previous submittal. Clarify these requirements. If this is a 3/4 HP unit then the current would be aprox. 7.6A, not 4.4A. Then provide proper overcurrent protection.
2. Demonstrate compliance with Tucson Lighting Code. This comment was made on the first submittal. When the Schedule per Section 8 of the Code is added to the plans, consider that this medium cutoff fixture, as documented on the cutsheet, is not full cutoff.
3. Demonstrate compliance with NEC 700.12 (F) regarding the circuiting of the exit and egress lighting.
10/15/2007 ROBERT SHERRY WATER REVIEW Approved
10/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the input of the gas-fired water heater: 40MBH or 50 MBH. Provide the height of the flue (from the hood to the cap) to show how it was sized.
2. Revise the size of the gas pipe to the unit heater; 1-1/4" required.
10/19/2007 VFLORES1 WWM REVIEW Needs Review
10/19/2007 ROGER BROOKS BUILDING-COMMERCIAL REVIEW Approved