Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03736
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03736 10/15/07 1. Mechanical shall provide Unit Heater Blower specifications and electrical requirements. Comment made on previous submittal. Clarify these requirements. If this is a 3/4 HP unit then the current would be aprox. 7.6A, not 4.4A. Then provide proper overcurrent protection. 2. Demonstrate compliance with Tucson Lighting Code. This comment was made on the first submittal. When the Schedule per Section 8 of the Code is added to the plans, consider that this medium cutoff fixture, as documented on the cutsheet, is not full cutoff. 3. Demonstrate compliance with NEC 700.12 (F) regarding the circuiting of the exit and egress lighting. |
| 10/15/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/15/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/15/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the input of the gas-fired water heater: 40MBH or 50 MBH. Provide the height of the flue (from the hood to the cap) to show how it was sized. 2. Revise the size of the gas pipe to the unit heater; 1-1/4" required. |
| 10/19/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 10/19/2007 | ROGER BROOKS | BUILDING-COMMERCIAL | REVIEW | Approved |