Permit Number: T07CM03736
Parcel: 13001004B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03736
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/28/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide the ventilation required for the restroom (75 CFM per water closet).
09/28/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a trap and vent for the trench drain.
2. Comment not addressed. Provide the sizes of the flues for the water heater and the unit heater. Provide sufficient information to show that they are properly sized and terminated.
09/28/2007 ROBERT SHERRY WATER REVIEW Denied Comment not addressed. Show the location and size of the required reduced pressure backflow preventer.
10/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03736 10/01/07

1. Indicate electrical requirements for Water Heater. Reference Sheet A3, General Mechanical Note 3.
2. Mechanical shall provide Heat Pump specifications and electrical requirements.
3. Mechanical shall provide Unit Heater Blower specifications and electrical requirements.
4. Provide fixture cut sheets for all exterior lighting.
5. Demonstrate compliance with Tucson Lighting Code.
6. Provide a lighting fixture schedule on the plans, with electrical requirements for all lighting fixtures.
7. Provide electrical requirements for the ceiling fans.
8. Demonstrate compliance with NEC 700.12 (F) regarding the circuiting of the exit and egress lighting.
9. Circuit 30 has a receptacle on the Electrical Plan. This is a spare on the panel schedule. Please clarify.
10/02/2007 PAUL MACHADO ENGINEERING REVIEW Approved
10/02/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
10/02/2007 MARTIN BROWN FIRE REVIEW Approved
10/15/2007 DROBEY1 WWM REVIEW Needs Review
10/15/2007 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/15/2007 DELMA ROBEY APPROVAL SHELF Completed
10/15/2007 DELMA ROBEY OUT TO CUSTOMER Completed
10/15/2007 DELMA ROBEY REJECT SHELF Completed