Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T07CM03723
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2007 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Activity: T07CM03723 Date: 10/5/07 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. I. GENERAL REQUIREMENTS: · Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. · As of June 13, 2007 the City of Tucson has adopted the 2006 IRC with the exception of the plumbing portion which has been replaced with the 2006 UPC with amendments. The plans should reference these codes § Provide consecutive sheet numbers on each construction drawing, R106.1.1. II. FLOOR PLANS: § Show the location of attic access (min. 22"x30"), catwalk and working platform for heating or air conditioning equipment located in the attic, R807, M1305.1.3. § Show size and type of all doors and windows, and designate the operable portion of windows, R310. III. PLUMBING PLAN: § Provide distinction between gas and water piping, UPC 301.1.1. IV. ELECTRICAL PLAN: · Clarify code year used (2006 IRC chapters 33 - 42). § Bathrooms require a separate 20-amp circuit, E3801.6. § Designate the circuit number for each light fixture, receptacle, appliance, and equip disconnect, E3603.5. V. INTERNATIONAL ENERGY CONSERVATION CODE: § Specify the "R" value of the insulation, as well as the "U" factor and the solar heat gain coefficient of the windows and doors. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1. If you have any questions please contact: Clayton Trevillyan (520) 837-4913 City of Tucson Residential Plan Review |
| 10/15/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | 1:SFR-UNIT #1 RECOUNTED ALL WASTEWATER PLUMBING FIXTURES-NEEDS 8TH FLOOR CREDIT EVALUATION 2:NEEDS WASTEWATER REVIEW OF EXSISTING LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/17/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 10/17/2007 | GERARDO BONILLA | REJECT SHELF | Completed |