Permit Number: T07CM03722
Parcel: 13110034A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03722
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/21/2007 DAVE MANN FIRE REVIEW Approved
09/27/2007 ROBERT SHERRY WATER REVIEW Denied 1. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 106.3.1, UPC 2006.
2. Revise the size of the water service into the building (1") to reduce the water velocity to 8 fps or less. Reference Table 604.4, footnote c, IPC 2006, as amended by the City of Tucson.
10/01/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2007 THAUSER1 OUT TO CUSTOMER Completed