Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM03722
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/21/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/27/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 106.3.1, UPC 2006. 2. Revise the size of the water service into the building (1") to reduce the water velocity to 8 fps or less. Reference Table 604.4, footnote c, IPC 2006, as amended by the City of Tucson. |
| 10/01/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/08/2007 | THAUSER1 | OUT TO CUSTOMER | Completed |