Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03703
Parcel: 107020130

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03703
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2007 ROBERT SHERRY WATER REVIEW Approved
11/15/2007 HEATHER THRALL ZONING REVIEW Approved
11/16/2007 MARTIN BROWN FIRE REVIEW Denied Please include approved water plan showing number and location of fire hydrants.
Please include flow data in design criteria (available from fire dept).
Be advised that stated design criteria and densities will not allow storage above 12' A.F.F.
11/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/19/2007 GBONILL1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2007 GERARDO BONILLA OUT TO CUSTOMER Completed