Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM03688
Parcel: 110120920

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T07CM03688
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2007 ANY ZONING REVIEW Active
09/10/2007 ANY WWM REVIEW Active
09/10/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
09/10/2007 ANY ENGINEERING REVIEW Active
09/10/2007 ANY FIRE REVIEW Active
09/11/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size to 1/8" minimum, all upper case.
09/11/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm03688 9/11/07

1. Supply keynote descriptions for Keynotes 5 and 6, Sheet E2.2.
2. Correct electrical loads on Ckts LP6-2, LP6-12 and LP6-16, and all others which may apply. Reference NEC 220.14 (I).
3. Minimum font size 1/8".
4. Add the following note in a prominent place on the plans: "All work in patient care areas shall comply with NEC 517.13."
09/11/2007 ROBERT SHERRY WATER REVIEW Approved
09/11/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approved
09/11/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font to 1/8" minimum and all upper case.
2. Revise the drawings to correspond to the scope of work.