Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/10/2007 | ANY | ZONING | REVIEW | Active | |
09/10/2007 | ANY | WWM | REVIEW | Active | |
09/10/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active | |
09/10/2007 | ANY | ENGINEERING | REVIEW | Active | |
09/10/2007 | ANY | FIRE | REVIEW | Active | |
09/11/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the font size to 1/8" minimum, all upper case. |
09/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm03688 9/11/07 1. Supply keynote descriptions for Keynotes 5 and 6, Sheet E2.2. 2. Correct electrical loads on Ckts LP6-2, LP6-12 and LP6-16, and all others which may apply. Reference NEC 220.14 (I). 3. Minimum font size 1/8". 4. Add the following note in a prominent place on the plans: "All work in patient care areas shall comply with NEC 517.13." |
09/11/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/11/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/11/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font to 1/8" minimum and all upper case. 2. Revise the drawings to correspond to the scope of work. |