Permit Number: T07CM03664
Parcel: 13323167B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03664
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: KGUN 9 - TI & SITE WORK
T07CM03664
Building Plan (1st Review)

TRANSMITTAL DATE: January 03, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Provide a copy of the last approved site or development plan so that zoning can verify the locations of the required handicapped parking and loading space.

3. Sheet A-100 Detail A, the proposed handicapped ramps do not show the location of the required detectable warning (truncated domes), see ICC/ANSI A117.1-2003 Sec. 406.13. Also so the proposed slopes for the proposed ramp.

4. It appears that the two (2) handicapped parking spaces and access aisles shown on the west end of Detail A, Sheet A-100 do not appear to have access to the sidewalk located to the south. Show the proposed accessible route for these handicapped parking spaces. The accessible route is not allowed to be located within the parking area access lane and/or behind the parking spaces. Accessible ramps with truncated domes are required at all access aisles.

5. The two (2) handicapped parking spaces and access aisles shown on the east end of Detail A, Sheet A-100 do not appear to have access to the sidewalk located to the south. Show the proposed accessible route for these handicapped parking spaces. The accessible route is not allowed to be located within the parking area access lane and/or behind the parking spaces. Accessible ramps with truncated domes are required at all access aisles.

6. Based on a development plan found on the TDOT Map site, the proposed new accessible route shown near the southwest corner of the building will encroach on a required loading space. This is not allowed. If relocating the loading space show the new location and maneuvering area on the plan.

7. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t07cm03664.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
12/31/2007 MATT FLICK ENGINEERING REVIEW Approved Incl. outside pavement demo & paving of less than 1 acre.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2008 CPIERCE1 OUT TO CUSTOMER Completed