Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/12/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
09/12/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/12/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The T&P relief cannot terminate in the washer box along with the washer drain unless it is a very special washer box. Show how this can be accomplished. |
09/12/2007 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
09/12/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/13/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03655 9/13/07 IECC calculations were required previous review. Demonstrate the correctness of a 3.1 W/SF allowance for a building area represented by this occupancy. Nowhere does the 2006 IECC allow this. |
09/25/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
09/25/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |