Permit Number: T07CM03655
Parcel: 13355231A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03655
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2007 TERRY STEVENS ZONING REVIEW Approved
09/12/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/12/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The T&P relief cannot terminate in the washer box along with the washer drain unless it is a very special washer box. Show how this can be accomplished.
09/12/2007 BIANCA RAMIREZ ENGINEERING REVIEW Approved
09/12/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/13/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03655 9/13/07

IECC calculations were required previous review. Demonstrate the correctness of a 3.1 W/SF allowance for a building area represented by this occupancy. Nowhere does the 2006 IECC allow this.
09/25/2007 VFLORES1 WWM REVIEW Needs Review
09/25/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review