Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03655
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/06/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the size of the proposed dryer exhaust duct (clarify the size - 5x3 or 6x3) conforms to the requirements of the dryer manufacturer. Reference Section 504.6, IMC 2006. |
| 09/06/2007 | RBROOKS1 | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. PROVIDE LIGHTING LOAD CALCULATION TO CONFIRM COMPLIANCE WITH THE IECC |
| 09/06/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/06/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE ACCESS INTO RESTROOM AS DEFINED BU ANSI A117.1 SECTION 404.2.3 2. PROVIDE ACCESS TO THE WASHER AND DRYER AS SPECIFIED BY ANSI A117.1 SECTION 611 AND 305 |
| 09/06/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide access to the cleanout currently located behind the water heater. 2. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Sections 103.2.3, 605.5, and 608.7 UPC 2006. |
| 09/12/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 09/12/2007 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 09/12/2007 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
| 09/12/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |