Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03646
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/03/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the waste and vent riser diagram with the floor plan. 2. Provide a vent for each floor sink. 3. Verify the the size of the waste piping (including the existing waste piping) complies with Table 7-5, UPC 2006. |
| 10/10/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |