Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03603 1/11/07

1. Please change #6 GND to #4 on the transformer secondary. Reference NEC Table 250.66 Note a.
2. Panel HB is new on the line diagram but existing on its schedule. Please clarify, and provide fault calculations for this panel if new.
3. It appears that there are 98A on the feeder to Panel HB, not 179A. Reference tallys at service on line diagram.
4. Panel HB is a 100A panel according to its schedule. Not protected by a 200AF. Please note that the original drawings called this a 200A panel.
5. Add WorkFlow for Mechanical.