Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03603
Parcel: 12701004C

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM03603
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03603 1/11/07

1. Please change #6 GND to #4 on the transformer secondary. Reference NEC Table 250.66 Note a.
2. Panel HB is new on the line diagram but existing on its schedule. Please clarify, and provide fault calculations for this panel if new.
3. It appears that there are 98A on the feeder to Panel HB, not 179A. Reference tallys at service on line diagram.
4. Panel HB is a 100A panel according to its schedule. Not protected by a 200AF. Please note that the original drawings called this a 200A panel.
5. Add WorkFlow for Mechanical.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2008 GERARDO BONILLA OUT TO CUSTOMER Completed