Permit Number: T07CM03601
Parcel: 13615001B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03601
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2007 STEVE SHIELDS ZONING REVIEW Approved
09/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03601 9/26/07

1. Panel Schedule A indicates new Panel. Line diagram refers to an existing breaker. Please clarify, new panel or existing.
2. Fault calculations "c" is for 3/0 AL. No such conductor on project.
3. Panel schedule indicates 200A panel. Not protected by a 400 A breaker.
4. Show location of electrical service on plans.
5. Account for Panel B on line diagram and in load calculations.
6. Rate Panel A for AFC.
09/26/2007 DAVE MANN FIRE REVIEW Approved
10/23/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/23/2007 GBONILL1 WWM REVIEW Needs Review
10/23/2007 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review