Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03601
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/26/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03601 9/26/07 1. Panel Schedule A indicates new Panel. Line diagram refers to an existing breaker. Please clarify, new panel or existing. 2. Fault calculations "c" is for 3/0 AL. No such conductor on project. 3. Panel schedule indicates 200A panel. Not protected by a 400 A breaker. 4. Show location of electrical service on plans. 5. Account for Panel B on line diagram and in load calculations. 6. Rate Panel A for AFC. |
09/26/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
10/23/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
10/23/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
10/23/2007 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |