09/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03599 9/26/07

1. Put identifying marks on fixtures on lighting plan. Not all fixtures on plan appear to be specified on lighting fixture schedule.
2. Condenser is specified as a 208V unit on Sheet M-2. Panel is 240V. Coordinate with Mechanical and clarify.
3. Conductors powering Panel M are undersized. 4/0 Al ampacity 180A. 3/0 Cu ampacity 200A. Panel A 400A.