Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03599
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03599 9/26/07 1. Put identifying marks on fixtures on lighting plan. Not all fixtures on plan appear to be specified on lighting fixture schedule. 2. Condenser is specified as a 208V unit on Sheet M-2. Panel is 240V. Coordinate with Mechanical and clarify. 3. Conductors powering Panel M are undersized. 4/0 Al ampacity 180A. 3/0 Cu ampacity 200A. Panel A 400A. |
09/26/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/26/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/01/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
10/01/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
10/01/2007 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
10/01/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |