Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03599
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/31/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
08/31/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, route, and termination of the condensate waste. 2. Provide an auxiliary drain for the air handler. 3. Show how the air handler and the condensing unit are to be mounted to the structure. |
08/31/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/31/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
09/26/2007 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
09/26/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
09/26/2007 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
09/26/2007 | DROBEY1 | WATER | REVIEW | Needs Review | |
09/26/2007 | DROBEY1 | ZONING | REVIEW | Needs Review | |
09/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/26/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |