Permit Number: T07CM03581
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: REVISION - - 6TH

Permit Number - T07CM03581
Review Name: REVISION - - 6TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T07CM03581, 4500 N Oracle Rd Old Macy's

Electrical plans for revision denied for following:

1. Sheet E 601, the feeder to Space 250A has been increased from 100 amp to 400 amp. The load summary for Pnl DP3B increased from 335 amps to 530 amps, 195 amps, where is this increase ?
2. Sheet E 602 show 2 excalators and a frieght elevator removed, the load summary remains the same ?


Ray Majuta
PDSD, City of Tuc,
Elect Pln Ck
4/30/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2010 CPIERCE1 OUT TO CUSTOMER Completed