Permit Number: T07CM03544
Parcel: 13629003A

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T07CM03544
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2008 TERRY STEVENS ZONING REVIEW Approved
01/24/2008 SREEVES1 ZONING HC SITE REVIEW Passed
01/24/2008 JOE LINVILLE LANDSCAPE REVIEW Approved
02/04/2008 WILLDAN ADA REVIEW Denied January 31, 2008

City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Lincoln Park Amphitheater and Gazebo (ADA/S) – 3rd REVIEW
CITY OF TUCSON LOG NO. T07CM03544
WILLDAN PROJECT NO. 13881-7077

The third review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable. This project has been reviewed for conformance ANSI A117.1-2003. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiners, David Williams, Site Accessibility.

ACCESSIBILITY COMMENTS:
General
Change all slopes to be ( 1 : X ) instead of ( X : 1). See redlines.

Sheet 5
An accessible route shall be provided to directly connect the performance area to the assembly seating area because a circulation path directly connects the performance area to the assembly seating area. An accessible route shall be provided from performance areas to ancillary areas or facilities used by performers. Reference the 2006 IBC Section 1108.2.7.

The sides of the stage are required to have handrails along the steps, apply detail 6 on sheet 9 to both sides of the steps for the stage. Reference ANSI A117.1-2003.

Sheet 6
Please show the slope and cross slope of the walking path. See redlines. Reference ANSI A117.1-2003.

Move the truncated domes from the center of the accessible ramp to the landing at the bottom of the ramp. See redlines for clarification.


Sincerely,
WILLDAN


David P. Gue, P.E.
City Engineer