Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03544
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 11/26/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | 11/26/07 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming. |
| 12/06/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The water demand for the two restrooms and the drinking fountain is 31 GPM and the drinking fountain requires a flowing water pressure of 30 PSI for proper operation. Given that the available water pressure at the recreation center is only 32 PSI (approximately 500 feet away) and that a reduced pressure backflow preventer is located at the rear of the restrooms (approximately a 10-PSI drop), how will the drinking fountain be able to be installed correctly? Also, the 2" water supply pipe is called out as 1" on the enlarged plan on sheet 12. |
| 12/06/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/10/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/26/2007 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Approved |