Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM03544
Parcel: 13629003A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03544
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
11/26/2007 TERRY STEVENS ZONING REVIEW Denied 11/26/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
12/06/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The water demand for the two restrooms and the drinking fountain is 31 GPM and the drinking fountain requires a flowing water pressure of 30 PSI for proper operation. Given that the available water pressure at the recreation center is only 32 PSI (approximately 500 feet away) and that a reduced pressure backflow preventer is located at the rear of the restrooms (approximately a 10-PSI drop), how will the drinking fountain be able to be installed correctly? Also, the 2" water supply pipe is called out as 1" on the enlarged plan on sheet 12.
12/06/2007 ROBERT SHERRY WATER REVIEW Approved
12/10/2007 GERRY KOZIOL WWM REVIEW Approved
12/26/2007 WILDAN BUILDING-COMMERCIAL REVIEW Approved