Permit Number: T07CM03526
Parcel: 13316024M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03526
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
08/27/2007 ANY ENGINEERING REVIEW Approved
08/28/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Denied 1. DOOR #9 IN OFICE DOES NOT HAVE THE REQUIRED APPROACH CLEARANCES. MINIMUM 18" REQUIRED PER ANSI A117.1 SECTION 404.2.3.4. RECOMEND REVERSING SWING OF DOOR TO OPEN OUT AGAINST WEST WALL.

2. SHEET E2 PROVIDE DOULE SWITCHING FOR ALL LIGHTING FIXTURES WITH MORE THAN ONE LAMP REFERENCE IECC505.2.2.1

3. PROVIDE THE ORIGINAL BUILDING SHELL PLANS FOR REFERENCE IN BALANCE OF REVIEW.
08/28/2007 DAVE MANN FIRE REVIEW Approved
08/30/2007 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
08/30/2007 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/30/2007 GBONILL1 WATER REVIEW Needs Review
08/30/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/30/2007 GBONILL1 WWM REVIEW Needs Review
08/30/2007 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2007 GERARDO BONILLA OUT TO CUSTOMER Completed