Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM03519
Parcel: 13502134B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03519
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference Sections 310.0 and 314.5, UPC 2006.
2. The temperature and pressure relief piping shall not terminate into a water heater pan. Reference section 508.5, UPC 2006.
3. All storage-type water heaters installed in a closed system require a listed expansion tank. Please show the expansion tank on plans. Reference Section 608.3, UPC 2006 with local amendments.
11/08/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review