Permit Number: T07CM03519
Parcel: 13502134B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03519
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approved
09/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified water heater does not limit the water temperature to less than 110 degrees Fahrenheit. Reference Section 413.1, UPC 2006. See also the water temperature data for Tucson Water at: http://www.tucsonaz.gov/water/docs/d200708.pdf
2. Provide the minimum plumbing facilities per Chapter 29, IBC 2006, as amended by the City of Tucson.
11/06/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review