| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2007 | RBROOKS1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/24/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/24/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified water heater does not limit the water temperature to less than 110 degrees Fahrenheit. Reference Section 413.1, UPC 2006. See also the water temperature data for Tucson Water at: http://www.tucsonaz.gov/water/docs/d200708.pdf 2. Provide the minimum plumbing facilities per Chapter 29, IBC 2006, as amended by the City of Tucson. |