Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM03519
Parcel: 13502134B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03519
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 STEVE SHIELDS ZONING REVIEW Approved
08/24/2007 LOREN MAKUS ENGINEERING REVIEW Approved
08/27/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations for the HVAC system per Section 403, IMC 2006.
2. Show the route and termination for the condensate drain for the rooftop unit.
08/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide listing information to show that the proposed water heater does not require a combination pressure temperature relief device per Sections 505 and 608, UPC 2006.
2. Clarify the termination of the cold water supply as shown in detail 2/M1 and how it relates to the manufacturer's installation instructions for the water heater.
3. Provide listing information for the flow control shown in detail 2/M1 and describe its function.
4. Show how the proposed water supply to the lavatory complies with the requirements of Section 413.1, UPC 2006.
5. Provide the minimum plumbing facilities per Chapter 29, IBC 2006, as amended by the City of Tucson.
08/27/2007 ROBERT SHERRY WATER REVIEW Approved
08/27/2007 GERRY KOZIOL WWM REVIEW Approved
08/28/2007 DAVE MANN FIRE REVIEW Approved
09/24/2007 CAGUILA1 BUILDING-COMMERCIAL REVIEW Approved 1. SHEET A2: PROVIDE A WALL FRAMING DETAIL. ILLUSTRATE THE ATTACHMENT OF THE WALL TO FLOOR ATTACHMENT AS WELL AS THE WALL TO FRAMING ABOVE.

2. Sheet A1: AT ENTRY INTO STOCK ROOM, THE OPPOSING DOORS ARE REQUIRED TO HAVE A MINIMUM OF 48' CLEARANCE BETWEEN THE DOORS IN THE FULLY OPENED POSITION. REFERENCE ANSI A117.1404.2.5
09/24/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review