Permit Number: T07CM03501
Parcel: 12409159A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03501
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
08/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM03501 8/24/07

1. Fixture K1, apparently incandescent, shall have a source efficiency of greater than 60 lumens per watt. Reference IECC 505.6.1.
2. Please remove the redundant GND on the line side of the service disconnect. The third 3/0 will carry fault current back to the source.
3. Water heaters are specified for 208V. Please coordinate with Plumbing and verify that 240V is acceptable. Plumbing shall indicate such on plans.
09/07/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/07/2007 RBROOKS1 BUILDING-COMMERCIAL REVIEW Approved 1. DETAIL VERTICAL BRAB BAR IN RESTROOM DETAIL

2. NOTE DRINKING FOUNTAIN @ SINK

3. NOTE THE MOP SINK IN THE RESTROOM
09/07/2007 ROBERT SHERRY WATER REVIEW Approved
09/07/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/07/2007 MARTIN BROWN FIRE REVIEW Approved
09/12/2007 GERRY KOZIOL WWM REVIEW Approved
09/12/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/12/2007 PAUL MACHADO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2008 SUE REEVES APPROVAL SHELF Completed
01/18/2008 VFLORES1 OUT TO CUSTOMER Completed