Permit Number: T07CM03497
Parcel: 14029212B

Review Status: Completed

Review Details: SITE

Permit Number - T07CM03497
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 DAVE MANN FIRE REVIEW Denied The fire turn radius on Sheets A1, A1.1 go over the curbs.

Remove the RP valve on the fire line on sheet C3 and show hydrant locations.

On sheet A-1 the vertical clearance shall be 15 feet.
08/29/2007 SREEVES1 ADA REVIEW Passed not a COT project
08/30/2007 DAVID RIVERA ZONING REVIEW Denied 08/30/07

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. Zoning cannot stamp the development plan as a site plan until CDRC has completed the review and approved the plan.

2. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the grading plan can be approved by Zoning. Two copies of the CDRC approved tentative plat/development plan, landscape and NPPO plans are to be submitted with the grading plan packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The tentative plat/development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the grading plans packet processed together for site approval.

3. As of this review date the Development plan (D07-0006) under the CDRC review process has not been approved.
08/30/2007 DAVID RIVERA ZONING HC SITE REVIEW Denied see zoning comments
09/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The rim elevation of the next upstream sanitary manhole (2628.11) is less than 12" below the first floor elevation (2628.90). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
2. Coordinate the location of the water service entrance and the direction of flow for the building sewer as shown on the site plan with the building plumbing plans.
09/21/2007 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Provide a copy of the approved development plan, landscape plan and Native Plant preservation plan with the next site plan submittal.
09/21/2007 PETER MCLAUGHLIN NPPO REVIEW Denied see landscapr comments
09/21/2007 JASON GREEN ENGINEERING REVIEW Denied 9-21-07

Development Services Department
Engineering Review Section

1. Engieering cannot stamp the development plan as a site plan until CDRC has completed the review and approved the plan.

2. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the site plan can be approved by Zoning. Two copies of the CDRC approved development plan, landscape and NPPO plans are to be submitted with the site plan packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The tentative plat/development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the site plan packet processed together for site approval.

3. As of this review date the Development plan (D07-0006) under the CDRC review process has not been approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
09/25/2007 CINDY AGUILAR REJECT SHELF Completed