Permit Number: T07CM03496
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03496
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. See: http://www.ci.tucson.az.us/tucsonwater/clearwater?output=allTabular
08/24/2007 ROBERT SHERRY WATER REVIEW Approved
08/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003.
3. Clarify the note calling for R-11 insulation.
08/31/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/31/2007 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
08/31/2007 DROBEY1 WWM REVIEW Needs Review
08/31/2007 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2007 DELMA ROBEY OUT TO CUSTOMER Completed