Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03496
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/24/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. See: http://www.ci.tucson.az.us/tucsonwater/clearwater?output=allTabular |
08/24/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/24/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2003. 3. Clarify the note calling for R-11 insulation. |
08/31/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
08/31/2007 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/31/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
08/31/2007 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/31/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |