Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03462
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/22/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
08/22/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
08/22/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03462 8/22/07 1. Note above panelboard schedule indicates a 35K-10K series rated system. This would clearly indicate that the main and branch circuit breakers on the panel are series rated with one another. The other note, under the fault calculations, refers to a 65K-10K system applicable to each downstream panel, without specification as to load side and line side devices. Please clarify. |
08/22/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/22/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | Correct occupant load to 49 maximum to allow for current exiting or install sprinkler system to make 1/3 longest diagonal acceptable for 2nd exit. |
08/22/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/22/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/22/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
08/22/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/22/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |