Permit Number: T07CM03462
Parcel: 11504471A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03462
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2007 TERRY STEVENS ZONING REVIEW Approved
08/22/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/22/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03462 8/22/07

1. Note above panelboard schedule indicates a 35K-10K series rated system. This would clearly indicate that the main and branch circuit breakers on the panel are series rated with one another. The other note, under the fault calculations, refers to a 65K-10K system applicable to each downstream panel, without specification as to load side and line side devices. Please clarify.
08/22/2007 ROBERT SHERRY WATER REVIEW Approved
08/22/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied Correct occupant load to 49 maximum to allow for current exiting or install sprinkler system to make 1/3 longest diagonal acceptable for 2nd exit.
08/22/2007 GERRY KOZIOL WWM REVIEW Approved
08/22/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/22/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/22/2007 MARTIN BROWN FIRE REVIEW Approved
08/22/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed