Permit Number: T07CM03444
Parcel: 12708187F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03444
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2007 MARTIN BROWN FIRE REVIEW Approved
10/24/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. NOTE 3A/DETAIL 1/A-2: PROVIDE 2X4 WEB BLOCKING AT ALL TOP AND BOTTOM TJI CORD FURR DOWN ATTACHMENTS
2. SUBSTITUTION OF A WATER COOLER FOR THE CODE REQUIRED ACCESSIBLE EWC MAY ONLY BE APPROVED BY THE BUILDING OFFICIAL IN WRITING.
10/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the sequence of operation (e.g. exhaust fans to be controlled with a time clock to run while the suite is occupied.) for the restroom exhaust fans on the drawing. Reference Section 403.2.1, IMC 2006.
10/26/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied An approved appeal to the building official is required prior to accepting a substitution for the drinking fountain. Reference Section 301.2, UPC 2006 and Section 2902.2, IBC 2006 (mercantile occupancy)

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed
10/30/2007 DELMA ROBEY REJECT SHELF Completed