Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03444
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/10/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/24/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NOTE 3A/DETAIL 1/A-2: PROVIDE 2X4 WEB BLOCKING AT ALL TOP AND BOTTOM TJI CORD FURR DOWN ATTACHMENTS 2. SUBSTITUTION OF A WATER COOLER FOR THE CODE REQUIRED ACCESSIBLE EWC MAY ONLY BE APPROVED BY THE BUILDING OFFICIAL IN WRITING. |
| 10/26/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the sequence of operation (e.g. exhaust fans to be controlled with a time clock to run while the suite is occupied.) for the restroom exhaust fans on the drawing. Reference Section 403.2.1, IMC 2006. |
| 10/26/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | An approved appeal to the building official is required prior to accepting a substitution for the drinking fountain. Reference Section 301.2, UPC 2006 and Section 2902.2, IBC 2006 (mercantile occupancy) |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/30/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 10/30/2007 | DELMA ROBEY | REJECT SHELF | Completed |