Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM03444
Parcel: 12708187F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03444
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2007 DAVE MANN FIRE REVIEW Denied The second exit cannot go through the stroage per IFC 1014.
08/21/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/22/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/11/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) Please clarify separated or nonseparated use in your code analysis pp A1. (ref section 508 of IBC)

2) Clarify how 2nd means of egress meets all of the requirements of section 1014.2 (2.2(2.4)) of the 2006 IBC.

3) Cieling soffit detail 1/A2 requires details information for stud spacing, brace spacing, size of screws, and alternative for plywood top and bottom cord suspension. (you may not attach to sides of plywood top and bottom cords).

4) Provide information for height of racks in storage. Rear exit sign may be blocked from view.

5) Separate plumbing facilities are required for each sex per section 2902.2 of the 2006 IBC.
09/17/2007 ROBERT SHERRY WATER REVIEW Approved
09/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for mercantile occupancy (e.g. two restrooms, a service sink, and a drinking fountain).
09/17/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2006.
09/19/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2007 VFLORES1 OUT TO CUSTOMER Completed
09/25/2007 VFLORES1 REJECT SHELF Completed