Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03444
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2007 | DAVE MANN | FIRE | REVIEW | Denied | The second exit cannot go through the stroage per IFC 1014. |
| 08/21/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/22/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/11/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Please clarify separated or nonseparated use in your code analysis pp A1. (ref section 508 of IBC) 2) Clarify how 2nd means of egress meets all of the requirements of section 1014.2 (2.2(2.4)) of the 2006 IBC. 3) Cieling soffit detail 1/A2 requires details information for stud spacing, brace spacing, size of screws, and alternative for plywood top and bottom cord suspension. (you may not attach to sides of plywood top and bottom cords). 4) Provide information for height of racks in storage. Rear exit sign may be blocked from view. 5) Separate plumbing facilities are required for each sex per section 2902.2 of the 2006 IBC. |
| 09/17/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/17/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for mercantile occupancy (e.g. two restrooms, a service sink, and a drinking fountain). |
| 09/17/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2006. |
| 09/19/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/25/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 09/25/2007 | VFLORES1 | REJECT SHELF | Completed |