Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03437
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/21/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Needs Review | |
08/21/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide auxiliary drain pans or secondary drain systems for fan coil units. Reference Section 307.2.3 IMC 2006. 2. Recirculation of ventilation air from toilet rooms is prohibited. Reference Section 403.2.1 (3), IMC 2003. 3. Provide mechanical energy code compliance calculations. |
08/21/2007 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
08/21/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/21/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/21/2007 | GBONILL1 | WWM | REVIEW | Needs Review | |
08/21/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing fixtures per Chapter 29, IBC 2006. 2. Show how the hot water temperature for the lavatories is to be limited to 110 degrees Fahrenheit. 3. Provide specifications for the shower mixing valve to show that it conforms to the requirements of Section 418.0, UPC 2006. 4. Show how the specified water heater is capable of meeting the hot water demand for the building. |
08/21/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
08/21/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
08/21/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/21/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |