Permit Number: T07CM03437
Parcel: 13219015C

Address:
2200 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03437
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2007 MICHAEL ST. PAUL ZONING REVIEW Needs Review
08/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide auxiliary drain pans or secondary drain systems for fan coil units. Reference Section 307.2.3 IMC 2006.
2. Recirculation of ventilation air from toilet rooms is prohibited. Reference Section 403.2.1 (3), IMC 2003.
3. Provide mechanical energy code compliance calculations.
08/21/2007 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/21/2007 ROBERT SHERRY WATER REVIEW Approved
08/21/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Needs Review
08/21/2007 GBONILL1 WWM REVIEW Needs Review
08/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing fixtures per Chapter 29, IBC 2006.
2. Show how the hot water temperature for the lavatories is to be limited to 110 degrees Fahrenheit.
3. Provide specifications for the shower mixing valve to show that it conforms to the requirements of Section 418.0, UPC 2006.
4. Show how the specified water heater is capable of meeting the hot water demand for the building.
08/21/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/21/2007 DAVE MANN FIRE REVIEW Approved
08/21/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2007 GERARDO BONILLA OUT TO CUSTOMER Completed