Permit Number: T07CM03400
Parcel: 135083950

Address:
7441 E 24TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM03400
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2007 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T07CM03400

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

· Interior alterations require the installation of smoke alarms if not existing, R313.2.1.

SECTIONS - DETAILS:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing (Details on A3.1), IRC table R702.3.5 footnote d.
2. Provide fiber-cement board rather than moisture resistant (green) gypsum board in tub and shower areas, R702.4.2.
3. Specify water-resistive barrier equivalent to two layers of Grade D paper over the wood based sheathing of exterior plaster wall coverings (Details on A2.1), R703.6.3.
4. Eave ventilation is not appropriate without attic space, or rafter cavity space between insulation and roof sheathing (Detail 2/A3.1), R806.1.

PLUMBING PLANS:

1. The City of Tucson has adopted the 2006 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). The plans should reference this code, or appeal to the Building Official for IRC design approval.
2. Note and specify all piping materials, UPC 301.1.1.

ELECTRICAL PLANS:

1. Specify the installation recessed lighting with 3" separation from combustibles or other listed conditions, R808, and comply with energy efficiency leakage, N1102.4.3.
2. Show the bathroom 20 AMP circuit separate from the exterior receptacle, E3603.4.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75 and ceilings is R=30 (batt requires a 9-½" cavity), N1102.1. Show these values on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.40, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/27/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
11/27/2007 CINDY AGUILAR REJECT SHELF Completed