Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM03397
Parcel: 114600830

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03397
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2007 STEVE SHIELDS ZONING REVIEW Needs Review
08/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font to a minimum size of 1/8", all upper case.
2. Specify the duct insulation.
08/15/2007 VFLORES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/15/2007 ROBERT SHERRY WATER REVIEW Approved
08/15/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
08/15/2007 VFLORES1 WWM REVIEW Needs Review
08/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font to a minimum size of 1/8", all upper case.
2. Provide a detail for the design of the the platform supporting the water heater.
3.Clarify the location of the trap primers - above the ceiling or 12" AFF per 20' of primer line?
4. Provide a water piping riser diagram.
5. Provide upper terminal cleanouts per Section 707.4, UPC 2006.
6. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. Reference Section 316.4.1, UPC 2006.
08/15/2007 ANY ENGINEERING REVIEW Approved
08/15/2007 DAVE MANN FIRE REVIEW Approved
08/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review