Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03397
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2007 | STEVE SHIELDS | ZONING | REVIEW | Needs Review | |
| 08/15/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font to a minimum size of 1/8", all upper case. 2. Specify the duct insulation. |
| 08/15/2007 | VFLORES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/15/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/15/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/15/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 08/15/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font to a minimum size of 1/8", all upper case. 2. Provide a detail for the design of the the platform supporting the water heater. 3.Clarify the location of the trap primers - above the ceiling or 12" AFF per 20' of primer line? 4. Provide a water piping riser diagram. 5. Provide upper terminal cleanouts per Section 707.4, UPC 2006. 6. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. Reference Section 316.4.1, UPC 2006. |
| 08/15/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 08/15/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |