| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 08/15/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03396 8/15/07 1. If the AC units are 45 FLA, they would be 5400VA per phase, not 3120. Panel may be overloaded if such is the case. 2. Please account for continuous load on panel schedule. 3. There is no Building Area Type in the 2006 IECC which conforms to this occupancy. |