Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03396
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
08/15/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03396 8/15/07 1. If the AC units are 45 FLA, they would be 5400VA per phase, not 3120. Panel may be overloaded if such is the case. 2. Please account for continuous load on panel schedule. 3. There is no Building Area Type in the 2006 IECC which conforms to this occupancy. |
08/15/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/15/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/15/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/20/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
08/20/2007 | CAGUILA1 | FIRE | REVIEW | Needs Review | |
08/20/2007 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
08/20/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |