Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM03396
Parcel: 116155090

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03396
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
08/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/15/2007 ROBERT SHERRY WATER REVIEW Approved
08/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/15/2007 HEATHER THRALL ZONING REVIEW Approved
08/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03396 8/15/07

1. If the AC units are 45 FLA, they would be 5400VA per phase, not 3120. Panel may be overloaded if such is the case.
2. Please account for continuous load on panel schedule.
3. There is no Building Area Type in the 2006 IECC which conforms to this occupancy.
08/20/2007 CAGUILA1 ENGINEERING REVIEW Needs Review
08/20/2007 CAGUILA1 WWM REVIEW Needs Review
08/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/20/2007 CAGUILA1 FIRE REVIEW Needs Review