Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM03395
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03395 8/15/07 1. For the conductors which have been sized at 1/0 on a 50A circuit to attenuate VD, it appears that the Equipment Grounding Conductor shall be sized at #1. Reference NEC 250.122 (B). 2. For the conductors which have been sized at #3 and #6 on a 20A circuit to attenuate VD, it appears that the Equipment Grounding Conductor shall be sized the same as the phase conductors. Reference NEC 250.122 (B). |