Permit Number: T07CM03395
Parcel: 133073450

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM03395
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03395 8/15/07

1. For the conductors which have been sized at 1/0 on a 50A circuit to attenuate VD, it appears that the Equipment Grounding Conductor shall be sized at #1. Reference NEC 250.122 (B).
2. For the conductors which have been sized at #3 and #6 on a 20A circuit to attenuate VD, it appears that the Equipment Grounding Conductor shall be sized the same as the phase conductors. Reference NEC 250.122 (B).