Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please show location of existing service disconnecting means, for 2924 E Broadway. Reference NEC 230.72, such disconnects shall be grouped.
2. Provide feeder size for the AC units.
3. Please remove the redundant #4 GND on the line side of both service disconnecting means. Keynote 10 on New Service diagram, Sheet E5. Reference NEC 250.24 (B).