| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please show location of existing service disconnecting means, for 2924 E Broadway. Reference NEC 230.72, such disconnects shall be grouped. 2. Provide feeder size for the AC units. 3. Please remove the redundant #4 GND on the line side of both service disconnecting means. Keynote 10 on New Service diagram, Sheet E5. Reference NEC 250.24 (B). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/21/2007 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 08/21/2007 | SUE REEVES | REJECT SHELF | Completed |