Permit Number: T07CM03379
Parcel: 12709001E

Address:
535 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03379
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2007 STEVE SHIELDS ZONING REVIEW Approved
08/14/2007 LOREN MAKUS ENGINEERING REVIEW Approved
08/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, International Building Code, 2006.
08/15/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) Please revise the door swing at room 1139 to provide the minimum maneuvering clearance for the pull side of the door per section 404.2.3 of ANSI 117.1-2003. In addition, please provide additional information regarding the new doors in rooms 1142 and 1149 to verify compliance with section 404.2.3. The lavatory in room 1149 appears to be within the maneuvering clearance.

2) Please provide additional information regarding the new sinks/lavatories in order to verify compliance with section 1109.3 of the 2006 IBC and section 606 of ANSI 117.1-2003.

3) Please provide verification that 20% has been spent upgrading the accessibility of the altered primary function areas in accordance with section3409.7 of the 2006 IBC. Please list the total valuation and detail the expenses associated with the accessibility upgrades.
08/15/2007 ROBERT SHERRY WATER REVIEW Approved
08/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, International Building Code, 2006.
2. Specify the insulation to be used on the HW and HWR piping.
08/27/2007 GBONILL1 WWM REVIEW Needs Review
08/27/2007 GBONILL1 FIRE REVIEW Needs Review
08/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review