Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM03371
Parcel: 140122210

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03371
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation calculations for the new occupancy. Reference Section 403.3, IMC 2006.
08/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/22/2007 GERRY KOZIOL WWM REVIEW Passed