Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM03371
Parcel: 140122210

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03371
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2007 HEATHER THRALL ZONING REVIEW Approved
08/14/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation calculations for the new occupancy. Reference Section 403.3, IMC 2006.
08/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/14/2007 ROBERT SHERRY WATER REVIEW Approved
08/14/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved Revised occupant load vfactor and occupant load
revised code from 2003 to 2006 for IMC, UPC and IFC
Redline requirement to insulate hot water and p-trap at lav.
08/14/2007 LOREN MAKUS ENGINEERING REVIEW Approved
08/14/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If hot water is supplied to the lavatory, show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Show how the waste and vent piping is to be modified. Reference Section 103.2.3, UPC 2006.
08/15/2007 DAVE MANN FIRE REVIEW Approved
08/15/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/17/2007 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2007 DELMA ROBEY OUT TO CUSTOMER Completed