Permit Number: T07CM03341
Parcel: Unknown

Address:
4146 N ORACLE RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM03341
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the termination of the roof drain leaders: detail 5/A7appears to terminate both the roof drain and the overflow with downspout nozzles over the sidewalk but sheet ASP-1 calls for termination with sidewalk scuppers. The overflow leader may terminate over a sidewalk with a downsout nozzle but the roof drain leader may not discharge onto a sidewalk.
2. Provide overflow capacity for the two scuppers draining the raised roof section on building 1.
3. The minimum width for each of the scuppers for building 2 is 12.57". Clarify the scupper width on detail 12/A7 and the call-out on sheet A2.1. The 5" downspout is adequate.
01/07/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2010 SUE REEVES OUT TO CUSTOMER Completed